2 cycle time, sampling rate, and shut-down time, Cycle time, sampling rate, and shut-down time, 12 appendix – JUMO 705001 mTRON T - Central Processing Unit Operating Manual User Manual
Page 149

149
12 Appendix
12.2
Cycle time, sampling rate, and shut-down time
Min.
Max.
Typical
PLC cycle time (FastTask)
1
7.5 ms
25 ms
(depending on tele-
gram repetitions)
10 ms
Adjustable PLC cycle time (Task)
2
50 ms
500 ms
-
System bus cycle time for
- Multichannel controller module
- 4-channel analog input module
- 8-channel analog input module
- Multifunction panel
30 ms
-
30 ms
System bus cycle time
1
for
- Relay module
- Digital input/output module
7.5 ms
-
10 ms
Multichannel controller module sampling
rate
2
-
-
50 ms
4-channel analog input module sampling
rate
2
-
-
50 ms
8-channel analog input module sampling
rate
2
-
-
375 ms
Relay module sampling rate
1
-
-
0 ms
Digital input/output module sampling rate
1
-
-
0 ms
Multifunction panel sampling rate
2
-
-
125 ms
Shut-down time (detection of module failure)
for
- Multichannel controller module
- 4-channel analog input module
- 8-channel analog input module
- Multifunction panel
-
-
100 to 750 ms
Shut-down time (detection of module failure)
for
- Relay module
- Digital input/output module
-
-
25 ms
1
Synchronous with system bus
2
Asynchronous with system bus