6 Configuration
Alarm
To open this window, use the "Alarm" button:
Parameters
Parameter
Selection/settings
Description
Alarm type 1, 2
Inactive
Monitoring is not active
Min. alarm
Alarm is issued if the limit value is not
met.
Max. alarm
Alarm is issued if the limit value is
exceeded.
Limit value 1, 2
-3.37E+38 to 0 to +3.37E+38
Limit value at which an alarm is issued.
Kind of alarm 1, 2 The alarm type is not set by default.
Collective alarm
Alarm is used to form the collective
alarm.
Event
Alarm results in an entry (event text) in
the event list.
Event text 1, 2
Use default text or select other text from
the list.
Text that is entered in the event list for
an alarm (for "Event" alarm type).
Switching differ-
ential
0 to 3.37E+38
Used to suppress constant switching
operations in the event of minor fluctua-
tions of the input signal around the limit
value.
Alarm suppress
Signal to activate the alarm suppression
Inactive
No alarm suppression
Module (source of signal)
Alarm suppression by a signal (high
active) that must be selected in the fol-
lowing field (digital selector).
Alarm delay
0 to 32767 s
Delay time for alarm activation
?
?
?