6 Configuration
Data format
Data format with which the interface is operated.
8 - 1 - no parity
8 data bits, 1 stop bit, no parity
8 - 1 - odd parity
8 data bits, 1 stop bit, odd parity
8 - 1 - even parity
8 data bits, 1 stop bit, even parity
Min response
time
0 to 40 to 500 ms
The minimum response time is adhered
to by the Modbus slave before a
response is sent following a data
request.
Modbus slave
Timeout mast.
60 to 10000 to 60000 ms
Master monitoring time
After this time, a timeout is identified in
the Modbus master. An internal digital
signal is set in the event of a timeout.
Modem active
Not selected (empty)
No modem operation (Modbus slave is
connected directly to serial bus).
Selected (checkmark)
Modem operation (Modbus slave is con-
nected to the Modbus master via the
modem).
Additional settings are required here
("Modem" button).
Modbus master
Timeout
60 to 200 to 10000 ms
A request sent by the master is defined
as faulty if no answer is received within
this time.
Scanning cycle
60 to 500 to 99999 ms
The Modbus master requests the Mod-
bus master data from the Modbus slave
at these intervals.
Parameter
Selection/settings
Description