Commissioning

6.2

Possible settings via DIP switch

30

Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2

Possible settings via DIP switch

[6-1]

DIP switch

E94YCIB001D

The following can be set via the S205 DIP switch:

• Number of the process data words

switches: 1 ... 4

( 31)

• Number of the parameter data words

switches: 5 and 6

( 32)

• Baud rate

switch: 8

( 33)

Lenze setting: All switches "OFF"
Switch 7 has no function.

Note!

• All DIP switches = "OFF" (Lenze setting):

At switch-on, the configuration from the codes gets active (

Settings in »Engineer«

( 34)

).

• At least one DIP switch = "ON":

At switch-on, the values are accepted from the switch positions.

• The data word sum (process data words + parameter data words) has to consist of

1 ... 10 words (16 bits/word).

• Switch off the voltage supply of the communication module and afterwards on again

to activate changed settings.