Interbus: internal error [0x00c86101, Interbus: internal mapping error [0x00c86110, Interbus: invalid parameter set [0x00c8641f – Lenze E94AYCIB User Manual

Page 51: Interbus: lenze setting loaded [0x00c86420, Interbus: invalid configuration [0x00c88125, 0x00c86101, 0x00c86110, 0x00c8641f, 0x00c86420, 0x00c88125

Advertising
background image

Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17

51

12

Error messages

12.2

Possible causes and remedies

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

INTERBUS: Internal error [0x00c86101]

INTERBUS: Internal mapping error [0x00c86110]

INTERBUS: Invalid parameter set [0x00c8641f]

INTERBUS: Lenze setting loaded [0x00c86420]

INTERBUS: Invalid configuration [0x00c88125]

INTERBUS: Reset of the communication stack [0x00c88126]

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

Send module with error description to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The selected PDO mapping is invalid:

• An object not supporting the required properties has

been specified.

• The data word sum (process data words + parameter

data words) has to consist of 1 ... 10 words (16 bits/

word).

Repeat

Configuring process data (PDO mapping) ( 37)

.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

No active parameter set could be loaded.

Download application again (including module).

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Access via standard device to the parameter set in the

memory module failed.

Download application again (including module).

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The active configuration is invalid:

• Process data words + parameter data words > 10

• Process data words + parameter data words = 0

The data word sum (process data words + parameter

data words) has to consist of 1 ... 10 words (16 bits/

word).

Adapt the number of process data words and parameter

data words:

• Process data words + parameter data words = 1 ... 10

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  warning  Information

Cause

Remedy

Error when processing the INTERBUS services

Execute renewed initialisation by the master.