Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17

45

10

Monitoring

10.1

Interruption of the INTERBUS communication

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10

Monitoring

10.1

Interruption of the INTERBUS communication

An interruption of the INTERBUS communication, e.g. by cable break or failure of the host (PLC,

master), is recognised by the communication module.
Responses to communication faults can be set in the Monitoring tab:

If the Servo Drive 9400 does not receive any valid process data in the "IBS-ACTIVE" state, the setting

in

C13885

/

C14885

is taken as a basis for the process data. (Like this the data sent last by the master

can be used or reset to zero.)

Settings in »Engineer«

( 34)

Settings

Description

Response to interrupted

INTERBUS communication

When the INTERBUS communication is interrupted, the response set here

(

C13880/1

/

C14880/1

) takes place in the inverter.

A change in the monitoring response becomes immediately effective.

Response time if the INTERBUS

communication is interrupted

If the "IBS-ACTIVE" status (INTERBUS active, cyclic data exchange) is left, the

response set under

takes place after the response time set here

(

C13881

/

C14881

) has elapsed.

• A value of "65535" in this code deactivates the monitoring function.

• A change in the monitoring is immediately effective.

• The monitoring time elapses when the "IBS-ACTIVE" status is left.

• After this response delay has elapsed, the response set is executed with

the error message "

INTERBUS: Data exchange stopped [0x00c88131]

"

( 52)

.