4 read/write, 5 get-od, Read/write – Lenze E94AYCIB User Manual

Page 42: Get-od, 9parameter data transfer

Advertising
background image

9

Parameter data transfer

9.3

Supported PMS services

42

Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.3.4

Read/Write

The "Read" PMS service reads parameters from the inverter. The inverter outputs the requested

parameter or an error message.
The "Write" PMS service writes on parameters of the inverter. The inverter outputs a positive

feedback or an error message.
The following error messages can occur:

9.3.5

Get-OD

The "Get-OD" PMS service reads out the object description for every parameter and data type.

Error Class

Error code

Additional

Code

[hex]

Description

6

3

0x00

No access authorisation

6

5

0x10

Impermissible job parameter

6

5

0x11

Invalid subindex

6

5

0x12

Data length too large

6

5

0x13

Data length too small

6

6

0x00

Object is no parameter

6

7

0x00

Object does not exist

6

8

0x00

Data types do not comply with each other

8

0

0x00

Request cannot be executed

8

0

0x20

Request cannot be executed at the moment

8

0

0x21

Cannot be executed because of local control

8

0

0x22

Cannot be executed because of device state

8

0

0x30

Quit value range / parameter can only be changed when the

controller is inhibited.

8

0

0x31

Parameter value too high

8

0

0x32

Parameter value too low

8

0

0x33

Sub parameter outside the value range

8

0

0x34

Value of the subparameter is too high

8

0

0x35

Value of the subparameter is too low

8

0

0x36

Maximum value is lower than minimum value

8

0

0x41

Communication object cannot be displayed on process data

8

0

0x42

Length of the process data exceeded

8

0

0x43

General collision with other values