Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
33
6
Commissioning
6.2
Possible settings via DIP switch
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2.3
Setting the baud rate
• The baud rate can be set via the switch 8.
• Set the baud rate according to the length of the bus cable between the single INTERBUS nodes.
• The current setting is displayed in the »Engineer« in
/
.
Note!
Select the baud rate which depends on the data volume, cycle time, and number of
nodes just high enough to suit your application.
DIP switch
Switch 8
Baud rate
Cable length between adjacent nodes
OFF
500 kbps
max. 400 m
ON
2 Mbps
max. 150 m
12345678
ON
OFF