Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17

33

6

Commissioning

6.2

Possible settings via DIP switch

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2.3

Setting the baud rate

• The baud rate can be set via the switch 8.
• Set the baud rate according to the length of the bus cable between the single INTERBUS nodes.
• The current setting is displayed in the »Engineer« in

C13863

/

C14863

.

Note!

Select the baud rate which depends on the data volume, cycle time, and number of

nodes just high enough to suit your application.

DIP switch

Switch 8

Baud rate

Cable length between adjacent nodes

OFF

500 kbps

max. 400 m

ON

2 Mbps

max. 150 m