Initialising PCP communication
40
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2
Initialising PCP communication
Make entries into the CRL (communication relation list) in order that communication between the
INTERBUS master and the communication module can take place.
Make the following entries in the CRL of the INTERBUS master:
Field name
Entry
Communication reference
2
Connection type
Master slave acyclic
Connection attribute
Defined
Max-PDU Sending-High-Prio
0
Max-PDU Sending-Low-Prio
64
Max-PDU Receiving-High-Prio
0
Max-PDU Receiving-Low-Prio
64
Supported Services Request
0x803000
Supported Services Response
0x000000
Maximum SCC
1
Maximum RCC
1
Maximum SAC
1
Maximum RAC
1