Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17

31

6

Commissioning

6.2

Possible settings via DIP switch

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2.1

Setting the number of process data words

• The number of process data words can be set via the switches 1 ... 4.
• 0 ... 10 process data words can be used.
• The current setting is displayed in the »Engineer« in

C13860/2

/

C14860/2

.

Note!

The data word sum (process data word + parameter data words) has to consist of 1 ... 10

words (16 bits/word).
Impermissible settings are reported by the BE LED (red blinking).

LED status displays

( 47)

The communication module then operates internally with the following values:

• 2 process data words (PD)
• 1 parameter data word (PCP)

DIP switch

Number of

PD

Switch

Max. number

of PCP

1

2

3

4

0

OFF

OFF

OFF

OFF

4

1

OFF

OFF

OFF

ON

2

OFF

OFF

ON

OFF

3

OFF

OFF

ON

ON

4

OFF

ON

OFF

OFF

5

OFF

ON

OFF

ON

6

OFF

ON

ON

OFF

7

OFF

ON

ON

ON

2

8

ON

OFF

OFF

OFF

9

ON

OFF

OFF

ON

1

10

ON

OFF

ON

OFF

0

12345678

ON

OFF