C14885 | clear process data, C14892 | pcp data length, C14892 – Lenze E94AYCIB User Manual

Page 68: C14885, Is ta, 13 parameter reference

Advertising
background image

13

Parameter reference

13.3

Parameters of the communication module for slot MXI2

68

Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C14881

C14885

C14892

Parameter | Name:

C14881 | Response time if the INTERBUS communication is interrupted

Data type: UNSIGNED_16

Index: 9694 = 0x25DE

If the "IBS-ACTIVE" status (INTERBUS is active and data is cyclically exchanged) is quit, the response parameterised

in

C14880/1

is executed after the monitoring time set for the data exchange has elapsed.

• A value of "65535" in this code deactivates the monitoring function.

• A change in the monitoring is immediately effective.

Interruption of the INTERBUS communication ( 45)

Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 65535 ms

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14885 | Clear process data

Data type: UNSIGNED_8

Index: 9690 = 0x25DA

Setting which process data of the inverters are to be further processed for maintaining the internal communication

if the INTERBUS failed.
Selection list

(Lenze setting printed in bold)

Info

0 Use of the last master process data
1 Process data are set to the value '0'

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14892 | PCP data length

Data type: UNSIGNED_8

Index: 9683 = 0x25D3

Setting of the number of the parameter data words to be used (PCP)

The setting is activated ...

• if all DIP switches (S205) are in the "OFF" position;

• after executing the "11: Save start parameters" device command via standard device code C00002 and

performing another mains switching of the communication module/drive afterwards.

Setting the number of process data words ( 31)

Selection list

(Lenze setting printed in bold)

Info

0 No PCB data
1 1 word
2 2 words
4 4 words

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT