Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17

61

13

Parameter reference

13.2

Parameters of the communication module for slot MXI1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13893

C13894

C13900

Parameter | Name:

C13893 | Process data length

Data type: UNSIGNED_8

Index: 10682 = 0x29BA

Setting of the number of the process data words to be used

The setting is activated ...

• if all DIP switches (S205) are in the "OFF" position;

• after executing the "11: Save start parameters" device command via standard device code C00002 and

performing another mains switching of the communication module/drive afterwards.

Setting the number of process data words ( 31)

Selection list

(Lenze setting printed in bold)

Info

0 No process data
1 1 word
2 2 words
3 3 words
4 4 words
5 5 words
6 6 words
7 7 words
8 8 words
9 9 words

10 10 words

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13894 | Baud rate

Data type: UNSIGNED_8

Index: 10681 = 0x29B9

setting the baud rate

The setting is activated ...

• if all DIP switches (S205) are in the "OFF" position;

• after executing the "11: Save start parameters" device command via standard device code C00002 and

performing another mains switching of the communication module/drive afterwards.

Setting the baud rate ( 33)

Selection list

(Lenze setting printed in bold)

Info

0 500 kbps
1 2.00 Mbps

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13900 | Firmware product type

Data type: VISIBLE_STRING

Index: 10675 = 0x29B3

Display of the product type (string with a length of 8 bytes)

• The following identification code is displayed: "E94AFCIB".

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT