Parameter reference

13.2

Parameters of the communication module for slot MXI1

60

Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13881

C13885

C13892

Parameter | Name:

C13881 | Response time if the INTERBUS communication is interrupted

Data type: UNSIGNED_16

Index: 10694 = 0x29C6

If the "IBS-ACTIVE" status (INTERBUS is active and data is cyclically exchanged) is quit, the response parameterised

in

C13880/1

is executed after the monitoring time set for the data exchange has elapsed.

• A value of "65535" in this code deactivates the monitoring function.

• A change in the monitoring is immediately effective.

Interruption of the INTERBUS communication ( 45)

Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 65535 ms

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13885 | Clear process data

Data type: UNSIGNED_8

Index: 10690 = 0x29C2

Setting which process data of the inverters are to be further processed for maintaining the internal communication

if the INTERBUS failed.
Selection list

(Lenze setting printed in bold)

Info

0 Use of the last master process data
1 Process data are set to the value '0'

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13892 | PCP data length

Data type: UNSIGNED_8

Index: 10683 = 0x29BB

Setting of the number of the parameter data words to be used (PCP)

The setting is activated ...

• if all DIP switches (S205) are in the "OFF" position;

• after executing the "11: Save start parameters" device command via standard device code C00002 and

performing another mains switching of the communication module/drive afterwards.

Setting the number of process data words ( 31)

Selection list

(Lenze setting printed in bold)

Info

0 No PCB data
1 1 word
2 2 words
4 4 words

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT