Installation

Electrical installation

If no repeater is to be used at the end of the segment, the bus must be terminated by

means of a bus terminating resistor at the last station (S). The bus termination is supplied

by this station.
An external supply of the communication unit provides for a supply of the bus termination

independent of the supply of the controller.



Bus termination

( 24)



External voltage supply

( 27)

Number of stations

[5-4]

Number of stations

Tip!
Repeaters do not have a station address. When calculating the maximum number

of stations, they reduce the number of stations by 1 on each side of the segment.
Repeaters can be used to build up line and tree topologies. The maximum total bus

system expansion depends on ...
• the baud rate used;
• the number of repeaters used.

Note!

The bus terminator must always be supplied. Otherwise, the bus can get

unstable.

2133PFB004

M

1

2

3

S

S

S

S

S

R

R

Segment

Master (M)

Slave (S)

Repeater (R)

1

1

31

-

2

30

-

2

-

30

1

3

-

30

1