3 digital and analog input information, Digital and analog input information, Digital and analog input information ( 40) – Lenze E84DGFCP User Manual

Page 40: Communication manual 8400 motec profibus

Advertising
background image

Communication manual 8400 motec PROFIBUS

Process data transfer

Digital and analog input information

40

L

EDS84DMOTPBUS EN 3.0 - 11/2011

8.3

Digital and analog input information

In addition to the process data, digital and analog input information can also be queried.

The signals are set permanently to 2 additional data words which must be parameterised

correspondingly in the HW manager.

Word

Bit

Function

Values / states

1

0

Analog input value (0 ... 10 V) 10 V = 1000

dec

(1111101000

bin

)

...
9
10

Digital input 3

0: Closed / not active

1: Open / active

11

Digital input 4

0: Closed / not active

1: Open / active

12

Digital input 5

0: Closed / not active

1: Open / active

13

Reserved

14

I/O status

0: I/O data are invalid.

1: I/O data are valid.

15

Drive status

0: Controller is 'offline'.

1: Controller ist 'online'.

2

0

RFR (controller enable)

0: Controller is enabled.

1: Controller is not enabled (inhibited).

1

Digital input 1

0: Closed / not active

1: Open / active

2

Digital input 2

0: Closed / not active

1: Open / active

3

Digital input 3

0: Closed / not active

1: Open / active

4

Digital input 4

0: Closed / not active

1: Open / active

5

Digital input 5

0: Closed / not active

1: Open / active

6

Reserved

...
13
14

I/O status

0: I/O data are invalid.

1: I/O data are valid.

15

Drive status

0: Controller is 'offline'.

1: Controller ist 'online'.

Advertising