C13920 | display: dip switch setting, C13950 | module internal communication status, C13920 – Lenze E84DGFCP User Manual

Page 88: Communication manual 8400 motec profibus

Advertising
background image

Communication manual 8400 motec PROFIBUS

Parameter reference

Parameters relevant for PROFIBUS communication

88

L

EDS84DMOTPBUS EN 3.0 - 11/2011

C13920

C13950

Parameter | Name:

C13920 | Display: DIP switch setting

Data type: UNSIGNED_8

Index: 10655

d

= 299F

h

Display of the current DIP switch setting

• The displayed value corresponds to the sum of the individual DIP switch values 1 ... 64.

• The active station address is displayed under

C13864

.



Setting the station address ( 31)

Display area

(min. value | unit | max. value)

0

255

;

Read access … Write access … CINH … PLC-STOP ; No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13950 | Module internal communication status

Data type: UNSIGNED_8

Index: 10625

d

= 2981

h

Display of the internal status of the communication unit
Selection list

(read only)

Info

0 Not initialized
1 Module ready for initialization
2 Reading Module parameters
3 Module Parameters has been read
4 Initialization of external protocol
5 Online
6 Module timeout

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT