EDS84DMOTPBUS EN 3.0 - 11/2011

L

79

Communication manual 8400 motec PROFIBUS

Error messages

Possible causes and remedies

Restart after watchdog reset [0x01bc6011]

Internal error [0x01bc6100]

Internal error [0x01bc6101]

Internal error [0x01bc6110]

Invalid parameter record [0x01bc641f]

Error: Lenze settings loaded [0x01bc6420]

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Communication unit is defective.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Communication unit is defective.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Communication unit is defective.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Communication unit is defective.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

No response … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

No active parameter set could be loaded.

Repeat the download of the application (including

module).

Response (Lenze setting printed in bold)

Setting: not possible

…

No response … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Access to the parameter set in the memory module via

the standard device failed.

Repeat the download of the application (including

module).