Communication manual 8400 motec profibus – Lenze E84DGFCP User Manual

Page 76

Advertising
background image

Communication manual 8400 motec PROFIBUS

Diagnostics

Diagnostic data

76

L

EDS84DMOTPBUS EN 3.0 - 11/2011

Error code of the Inverter Drive 8400 motec
If an error occurs in the controller, the logbook saves a 32-bit value in an error format which

consists of the following information:

[11-1] Structure of the error number

 Bytes 13 ... 16 of the diagnostic message contain the error code of the controller.
 In the logbook and in code C00165, the error number is shown in the following syntax

in order to facilitate the readability:
[Error type].[Error field no.].[Error ID]

Example: Error "Short circuit (OC1)"

A Reserved

B Error type
C Error subject area

D Error ID

2

1

0

3

Bit

16

25

26

31

0

15

29

30

Software manual/»Engineer« online help for Inverter Drives 8400 motec
Here you'll find detailed information on the structure and contents of the error

codes.

Byte

Value

[hex]

Description

1

x Standard data (PRM_Fault)

...

6
7

0A Block length of the advanced diagnostics = 10 bytes

8

81 Status message

9

00 Slot 0

10

01 Status coming

11

00

12

00

13

0B Error message 0x11C4000B ("Short circuit (OC1)")

• Error type: "Warning locked"

• Subject area: 0x11C4 (current)

• Error ID: 0x000B

Thus, the error number "0x11C4000B" means: An overcurrent has been detected in

the "current" subject area. This overcurrent causes a "Warning locked" error

response which has to be unlocked after the error has been removed.

14

00

15

C4

16

11

Advertising