PROFIBUS communication faults can be diagnosed via the LEDs of the communication unit.
Moreover, the »Engineer« provides PROFIBUS diagnostic information.

11.1

LED status displays

E84DG056

LED

Colour

State

Description

MS

Green

On

The communication module is supplied with voltage and has

established a connection to the standard device.

Blinking

The communication module is supplied with voltage, but has not yet

established a connection to the standard device. (Standard device is

switched off, initialising or not present.)

ME

Red

On

An error concerning the communication module has occurred.

BS

Green

Off

The communication module is not active on the fieldbus or is in the

"Init" state.

Blinking

The communication module is in the "Data_Exchange" state.

BE

Red

Blinking

Incorrect setting for the station address.

The communication module is initialised and internally operates

with the respective default values.

On

Bus error/fault is active (e.g. bus cable unplugged).