EDS84DMOTPBUS EN 3.0 - 11/2011

L

41

Communication manual 8400 motec PROFIBUS

Parameter data transfer

Addressing of the parameter data

9

Parameter data transfer

The PROFIBUS communication unit supports the cyclic and acyclic transmission of

parameter data:

 Cyclic DP-V0 parameter data are based on the DRIVECOM profile.

If the DP-V0 parameter data channel is active, it additionally occupies 4 words of the

input and output data.

 The acyclic DP-V1 parameter data are based on the PROFIdrive profile (PROFIDrive (DP-

V1) in preparation)

9.1

Addressing of the parameter data

The parameter data are addressed via codes which are listed in a code table in this

documentation and in the corresponding documentation of your controller.



Parameter reference

( 81)

Addressing of Lenze parameters
In the case of the DP-V0 parameter data channel, the parameters of a device are not

addressed directly via Lenze code numbers, but via indices (bytes 3 + 4) and subindices

(byte 2).

 The conversion is made via an offset (24575 / 0x5FFF):

– PROFIBUS-Index

dec

= 24575 - Lenze code numbers

– PROFIBUS-DP index

hex

= 0x5FFF - Lenze code number

hex

 Example of C00105 (quick stop deceleration time):

– PROFIBUS-Index

dec

= 24575 - 105 = 24470

– PROFIBUS-DP index

hex

= 0x5FFF - 0x69 = 0x5F96

 The parameter values are entered into the user data (bytes 5 to 8) of the telegram.