Short-time interruption of profibus communication, Communication manual 8400 motec profibus – Lenze E84DGFCP User Manual

Page 70

Advertising
background image

Communication manual 8400 motec PROFIBUS

Monitoring

Short-time interruption of PROFIBUS communication

70

L

EDS84DMOTPBUS EN 3.0 - 11/2011

10.2

Short-time interruption of PROFIBUS communication

[10-1] Sequence for short-time interruption of communication

The master detects the communication fault and only after a few microseconds it transfers

the slave to the WAIT_PRM state of the DP state machine (see fig.

[10-1]

).

Only after the state chain of the DP state machine ending in the "Data_Exchange" state

(DATA_EXCH) has been passed through, the watchdog monitoring time calculated for the

slave (in milliseconds) continues to run.

Additional monitoring for the data exchange
An additional monitoring function for data exchange is available under code

C13881

. This

monitoring function already becomes active when the "Data_Exchange" state is exited

and the parameterised time (0 ... 65535 ms) has expired. The monitoring function then

triggers the response parameterised under

C13880/1

.

2133PFB006

POWER ON

WAIT_PRM

WAIT_CFG

DATA_EXCH

Slave_Diag
Get_Cfg

Set_Slave_Add

Slave_Diag

Chk_Cfg, not o.k.
Set_Prm, not o.k.

Chk_Cfg, o.k.

Slave_Diag
Set_Prm
Get_Cfg

Note!

The watchdog monitoring time does not continue to run when the slave does

not reach the "Data_Exchange" state due to repeated communication errors

(e.g. caused by loose contact).

Note!

Observe the following condition for the time setting:
Monitoring time for data exchange (

C13881

)

watchdog monitoring time of

PROFIBUS (

C13882/1

).