Communication manual 8400 motec PROFIBUS
Monitoring
Settings and displays in the »Engineer«
10.3
Settings and displays in the »Engineer«
For monitoring the PROFIBUS communication, you can set a Lenze-internal monitoring
time (
) and a response of the controller
(
) in the »Engineer« via the
Monitoring tab.
The watchdog monitoring time
defined in the PROFIBUS master is displayed in code
.
If the controller does not receive any valid process data when being in the
"Data_Exchange" state, the process data are handled according to the setting in
. (The last data sent by the master can either be used or set to zero.)
Moreover, you can set the error responses in the controller that cause a setting of the
external diagnostic bit ("Diag-Bit")
(