10 monitoring, 1 permanent interruption of profibus communication, Monitoring – Lenze E84DGFCP User Manual

Page 69: Permanent interruption of profibus communication, Communication manual 8400 motec profibus

Advertising
background image

EDS84DMOTPBUS EN 3.0 - 11/2011

L

69

Communication manual 8400 motec PROFIBUS

Monitoring

Permanent interruption of PROFIBUS communication

10

Monitoring

10.1

Permanent interruption of PROFIBUS communication

If the PROFIBUS communication is interrupted permanently, e.g. by cable breakage or

failure of the PROFIBUS master, no process data are transmitted to the slave being in the

"Data_Exchange" state.
After the watchdog monitoring time determined by the PROFIBUS master has expired, the

response parameterised in

C13880/1

is executed.

The process data handling depends on the setting in

C13885

. (The last data sent by the

master can either be used or set to zero.)

Preconditions for a controller (slave) response

 A monitoring time of 1 ... 65534 ms is set for the "Data_Exchange" state (

C13881

).

A value of "65535 ms" (Lenze setting) deactivates the monitoring.

 A response is set for the slave in

C13880/1

(Lenze setting: "No response").

 The slave is in the "Data_Exchange" state.
 The watchdog monitoring time is configured correctly in the master.

If one of these preconditions is not met, the response to the absence of cyclic process data

telegrams from the master is not executed.



Settings and displays in the »Engineer«

( 71)