Installation

Electrical installation

5.2.5

External voltage supply

 By means of the external voltage supply, PROFIBUS communication for commissioning

can be established, and the data of the digital and analog inputs can be queried.

 Furthermore the external voltage supply serves to maintain PROFIBUS communication

if the main supply fails.

 The digital inputs RFR, DI1 ... DI5 and the analog input can continue to be evaluated.
 The external voltage supply is done via the terminals 24E and GND of the terminal strip

X3.

 Permissible voltage (DC) / max. current:

– U = 24 V DC (20 V - 0 % ... 29 V + 0 %)
– I

max

= 400 mA

 Access to parameters of a device that is disconnected from the mains is not possible.