4-5

BA2131EN

Wiring features:

Features:

Communication medium

RS485

Network topology

without repeater: line
with repeater: line or tree

Possible number of controllers

without repeater: 32
with repeater: 127

Maximum cable length

1200 m (depending on the baud rate and the cable type used)

Maximum baud rate

9.6-12000 kbit/s

The connection of the bus system PROFIBUS-DP is shown in the survey drawing. The required
accessories (e.g. connection cables) are listed in chapter 8.1.

1

93XX

82XX

2

3

8200 vector

Fig. 4-3

PROFIBUS with RS485 wiring (without repeater)
1

Host

2

Bus-connector (

ž

4-6)

3

Bus cable (

ž

4-6)

Wiring

Warning!

l

If the 2131 fieldbus module is no longer supplied with voltage, the bus system will continue
operation. However, the connected controller can no longer be accessed from the host.

l

If single bus participants are to be disconnected, it must be ensured that the bus terminators
at the physical cable ends remain active.

l

Only use cables which correspond to the listed specifications (see chapter 8.1).

l

Observe the bus connector drawing.

(

ž

4-6)

l

Connect the controller using the bus connector.
Note: The bus system will not be interrupted if the bus connector is pulled off the controller.

l

Connect a bus terminator to the physical bus ends. The bus terminator is integrated into the
bus connector and can be activated via a switch.

l

Observe the wiring notes and the documentation for the control system.