Commissioning

5-1

BA2131EN

5

Commissioning

Stop!

l

Before switching on the mains voltage check the wiring for completeness, short circuit and
earth fault.

l

Keep to the switch-on sequence!
(Chapter 5.1 to chapter 5.2.2)

5.1

Configuration of the host system for communication with the
2131 fieldbus module.

The Lenze controllers are PROFIBUS-DP participants in conformity with standards. Communication
with the Simatic-S5 is possible, provided that the following Siemens hardware and software
components are available:

l

S5-interface module IM308-B or IM308-C

l

Programming software COM-ET200

The COM-ET200 software is available in a DOS version (COM-ET200 DOS) and in a Windows
version (COM-ET200 WIN). The following two sections explain the specific controller settings for
both versions. The third section gives a program example which is to support the commissioning.

5.1.1

Settings with COM-ET200 DOS

In the following, we describe how to configure a Lenze controller for the program package COM-ET
200 DOS:

1. Copy the file LE00AATD.200 from the diskette to the COM-ET200 directory.

2. Fill in the boxes of the menus indicated then:

Menu: ET200 system parameter

Bus profile:

DP standard

Menu: Configure

Station type:

Lenze 2131 Vxx

Configuration: User data with DP parameter-setting channel

0. = 115; 1. = 113 oder
0. = 115; 1. = 114

User data without DP parameter-setting channel

0. = 113 or
0. = 114

5.1.2

Settings with COM-ET200 WIN

In the following we describe how to configure a Lenze controller for the program package
COM-ET200 WIN:

1. Copy the file LE00AAAX.200 from the diskette to the COM-ET200 directory.

2. Select the 2131 fieldbus module via the slave family DRIVES.