3 profibus-dp parameter-setting channel, 1 structure of the dp parameter-setting channel, Profibus-dp parameter-setting channel – Lenze 2131IB User Manual

Page 28: Structure of the dp parameter-setting channel, Parameter setting

Advertising
background image

Parameter setting

6-5

BA2131EN

l

3 words process data; label 72

hex

(114)

PIW/POW 1

PIW/POW 2

PIW/POW 3

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

l

DP parameter-setting channel

1)

+ 2 words process data;

label 73

hex

71

hex

(115, 113)

DP parameter-setting channel

PIW/POW 1

PIW/POW 2

Byte 1

Byte 8

Byte 9

Byte 10

Byte 11

Byte12

1) see chapter 6.3

l

DP parameter-setting channel

1)

+ 3 words process data;

label 73

hex

72

hex

(115, 114)

DP parameter-setting channel

PIW/POW 1

PIW/POW 2

PIW/POW 3

Byte 1

Byte 8

Byte 9

Byte 10

Byte 11

Byte 12

Byte 13

Byte 14

1) see chapter 6.3

6.3

PROFIBUS-DP parameter-setting channel

The PROFIBUS DP parameter-setting channel offers a parameter setting and diagnostics possibility
for controllers. It is therefore possible to access all Lenze parameters (codes).

If the DP parameter-setting channel is active, it assigns the first 8 bytes of the and input and output
data. The DP parameter-setting channel has the same structure for both transmission directions.

6.3.1

Structure of the DP parameter-setting channel

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Service

Subindex

Index
High byte

Index
Low byte

Data 4
(Error 4)

Data 3
(Error 3)

Data 2
(Error 2)

Data 1
(Error 1)

Byte 1: Service

Job and response control for the DP parameter-channel.

Bit no. Meaning

0 - 2

Service
Job for the controller. The bits are set only by the master.

l

0 = no job

l

1 = read job (read data from the controller)

l

2 = write job (write data to the controller)

3

Reserved

4 - 5

Data length
Length of the data in the field data/error.

l

0 = 1 byte

l

1 = 2 byte

l

2 = 3 byte

l

3 = 4 byte

6

Handshake
Indicates a new job. The master changes this bit for every new job. The controller copies the bit to its response message.

7

Status
Status information from the controller to the master when sending acknowledgement. This bit informs the master whether the job
was carried out without faults.

l

0 = Job completed with fault.

l

1 = Job not completed. A fault occured. The data in the field Data/Error are interpreted as error message.