1 process-data assignments for 82xx, 2 process-data assignment for 8200 vector, Process-data assignments for 82xx – Lenze 2131IB User Manual

Page 33: Process-data assignment for 8200 vector, Parameter setting

Advertising
background image

Parameter setting

6-10

BA2131EN

6.4.1

Process-data assignments for 82XX

Structure of the PO-data response (data to drive)

Byte 1

Byte 2

Byte 3

Byte 4

DRIVECOM control word
High byte

DRIVECOM control word
Low byte

Setpoint
High byte

Setpoint
Low byte

DRIVECOM control word: see chapter 6.5.3 or chapter 6.5.2.

Setpoint: frequency setpoint
Here the frequency setpoint is preselected as process data word. The standardization differs from
C0046. It is indicated with a sign:

б

24000 =

б

480 Hz.

Structure of the PI data response (data from drive)

Byte 1

Byte 2

Byte 3

Byte 4

DRIVECOM status word
High byte

DRIVECOM status word
Low byte

Actual value
High byte

Actual value
Low byte

DRIVECOM status word: see chapter 6.5.4 or chapter 6.5.2.

Actual value: act. frequency value
The actual frequency value is indicated with a sign:

б

24000 =

б

480 Hz.

6.4.2

Process-data assignment for 8200 vector

Structure of the PO data response

Digital and analog input and output signals can be freely configured (see Operating Instructions for
8200 vector; codes C0410, C0412, C0417 and C0421)

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

DRIVECOM
Control word
High byte

DRIVECOM
Control word
Low byte

AIF-IN.W1
High byte

AIF-IN.W1
Low byte

AIF-IN.W2
High byte

AIF-IN.W2
Low byte

Structure of the PI-data response

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

DRIVECOM
Status word
High byte

DRIVECOM
Status word
Low byte

AIF-OUT.W1
High byte

AIF-OUT.W1
Low byte

AIF-OUT.W2
High byte

AIF-OUT.W2
Low byte

Show/Hide Bookmarks