Troubleshooting and fault elimination

7-4

BA2131EN

7.2

Check PROFIBUS

Short testing of the PROFIBUS system in the event of faulty initialization. The diagnostics information
of the PROFIBUS fieldbus modules in the host must be considered.
For troubleshooting it can be reasonable to reduce the bus so that only one unit is connected to the
PROFIBUS.

Switch on all units or

disconnect all switched-off

units from the PROFIBUS

Are all units

connected to the

PROFIBUS

switched on?

PROFIBUS
initialization

ok?

yes

Reduce the number of
units connected to the

PROFIBUS

until the unit in question is

the last one connected.

Reconnect a unit

no

yes

Replace the unit

no