2 drivecomunit control, Drivecom unit control, Parameter setting – Lenze 2131IB User Manual

Page 37: 2 drivecom unit control

Advertising
background image

Parameter setting

6-14

BA2131EN

Status word xxxx xxxx x0xx 0000

NOT READY TO SWITCH ON

QSP**

Ctrl. enable**

Ctrl. inhibit**

automatically when
initializing is com-
pleted

TRIP (fault)

TRIP reset**

Switch on unit

READY TO SWITCH ON

Status word xxxx xxxx x01x 0001

SWITCHED ON

Status word xxxx xxxx x01x 0011

OPERATION ENABLED

Status word xxxx xxxx x01x 0111

automatically

Fault

Status word xxxx xxxx x0xx 1000

Note:
The terms marked with ** are
commands

Fig. 6-3

Status diagram for standard unit control

Status

Meaning

NOT READY TO SWITCH
ON

The controller is being initialized and is not yet ready to operate.
It then automatically switches to the status READY TO SWITCH ON.

READY TO SWITCH ON

The controller is inhibited and waits for the power stage to be charged. It then automatically switches to the status “SWITCHED ON“.

SWITCHED ON

The controller is inhibited and waits for controller enable.

OPERATION ENABLED

The controller is enabled. In this status, a pulse inhibit can be set automatically.

FAULT

The controller is in the status “FAULT“ (TRIP).

6.5.2

DRIVECOM unit control

With PROFIBUS control (for 82XX: Lenze parameter L-C0001 = 3; for 93XX: always) and when using
the 2131 fieldbus module, Lenze controllers have a controller status as standardized in the
DRIVECOM profile 20.

Information about the current unit status (Fig. 6-4, see below) (rectangles) are available in the
DRIVECOM parameter “ status word“ . Commands in the DRIVECOM parameter control word can
change the controller status. These commands are marked by arrows in the following diagram.