6 lenze-specific parameters, 2 parameter l-c0142, Lenze-specific parameters – Lenze 2131IB User Manual

Page 45: Parameter l-c0142, Parameter setting

Advertising
background image

Parameter setting

6-22

BA2131EN

6.6

Lenze-specific parameters

6.6.1

Only 82XX: Lenze parameter Operating Mode (L-C0001)

Parameter
name
(Index)

Sub-I
ndex

Data
str.

Data
type

Meaning
(Initialization is printed in bold)

Operating
mode
(5FFE

hex

)

0

S

I32

Value

Control source

Setpoint source

Parameter source

0

Terminal

Terminal

PROFIBUS

1

Terminal

8201 (keypad)

PROFIBUS

2

Terminal

Terminal

PROFIBUS

3

PROFIBUS

PROFIBUS

PROFIBUS

6.6.2

Parameter L-C0142

This parameter L-C0142 prevents the drive from uncontrolled restarts after:

l

Mains connection and disconnection

l

Internal fault

l

Internal message (with pulse inhibit) > 0.5 s

If the controller sets the status “ Mesage“ because of an internal fault (e. g. short mains failure) and
the fault remains active longer than 0.5 s, the controller will be inhibited automatically.

The parameter L-C0142 has the following function:

l

L-C0142 = 1:
The controller restarts automatically as soon as the fault is not active any longer

l

L-C0142 = 0:
The controller remains inhibited and the drive cannot restart even if the fault is no longer
active.
– The drive restarts after a LOW-HIGH transition at one of the inputs for “ Controller inhibit“

(CHIN, e. g. at terminal X5/28)