3 rated data, 4 dimensions, 5 protocol data – Lenze EMF2112IB User Manual

Page 10: Rated data, Dimensions, Protocol data, Technical data

Advertising
background image

Technical data

3-2

BA2112EN

3.3

Rated data

Field

Values

Communication medium

ASIC LPCII

Supply voltage

Voltage supply via INTERBUS-Loop.

Insulation voltage - bus systems:

to PE

50 V AC

to external supply (terminal 39/59)

0 V

(no electrical isolation)

to power stage

– 820X / 821X

270 V AC

(single basic insulation)

– 822X / 93XX / 8200 vector

270 V AC

(double basic insulation)

to the control terminals

– 8200 vector

100 V AC

(single basic insulation)

– 820X

0 V

(no electrical isolation)

– 821X

50 V AC

(electrical isolation)

– 822X / 93XX

270 V AC

(single basic insulation)

to external bus system

0 V

(no electrical isolation)

Degree of pollution

VDE 0110 part 2 pollution degree 2

3.4

Dimensions

18

75.2

61.8

INTERBUS loop

2112

IN

OUT

Fig. 3-1

Dimensions of the 2112 fieldbus module

3.5

Protocol data

Field

Values

Maximum number of controllers with InterBus-Loop 2112

36

Process-data words (PCD):

2 words (32 bit)

INTERBUS-Loop identification

179 (decimal) or B3 (hex)

Baud rate

500 kbit/s

Show/Hide Bookmarks