Parameter setting

6-10

BA2112EN

6.1.2.2

Status word

Status word for 82XX and 8200 vector

820X

821x,822x

8200vector
Lenze setting

0

Reserved

Actual parameter set
0 = Parameter set 1 or 3 active
1 = Parameter set 2 or 4 active

DCTRL-PAR-B0

1

IMP (pulse inhibit)
0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited

IMP (pulse inhibit)
0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited

DCTRL1-IMP

2

I

max

(current limit reached)

0 = Current limit not reached
1 = current limit reached

I

max

(current limit reached)

0 = Current limit not reached
1 = current limit reached

MCTRL1-IMAX

3

Reserved

f

d

= f

dset

0 = f

d

f

dset

1 = f

d

= f

dset

MCTRL1-RFG1= NOUT

4

f

d

= f

dset

0 = f

d

f

dset

1 = f

d

= f

dset

RFG on = RFG off
0 = RFG on

RFG off

1 = RFG on = RFG out

NSET1-RFG1-I= 0

5

Qmin (f

d

f

dQmin

)

0 = Qmin not active
1 = Qmin active

Qmin (f

d

f

dQmin

)

0 = Qmin not active
1 = Qmin active

PCTRL1-QMIN

6

f

d

= 0 (act. frequency = 0)

0 = f

d

0

1 = f

d

= 0

f

d

= 0 (act. frequency = 0)

0 = f

d

0

1 = f

d

= 0

DCTRL1-NOUT= 0

7

Ctrl. inhibit (controller inhibit)
0 = controller not inhibited
1 = controller inhibited

Ctrl. inhibit (controller inhibit)
0 = controller not inhibited
1 = controller inhibited

DCTRL1-CINH

8...11 Unit status

0 = No error
8 = Error active

Unit status

0 = Controller initialization
1 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active

8 = Fault active

Unit status

0 = Controller initialization
1 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active

8 = Fault active

12

Overtemperature warning (

ϑ

max

- 10°C)

0 = No warning
1 = Warning

Overtemperature warning
0 = No warning
1 = Warning

DCTRL1-OH-WARN

13

U

Gmax

(DC-bus overvoltage)

0 = No overvoltage
1 = overvoltage

U

Gmax

(DC-bus overvoltage)

0 = No overvoltage
1 = overvoltage

DCTRL1-OV

14

Direction of rotation
0 = CW rotation
1 = CCW rotation

Direction of rotation
0 = CW rotation
1 = CCW rotation

DCTRL1-CCW

15

Ready for operation
0 = not ready for operation
1 = ready for operation

Ready for operation
0 = not ready for operation
1 = ready for operation

DCTRL1-RDY

Show/Hide Bookmarks