4 installation, 1 connections of the fieldbus module 2112, Connections of the fieldbus module 2112 – Lenze EMF2112IB User Manual

Page 13: Installation, 4installation

Advertising
background image

Installation

4-1

BA2112EN

4

Installation

4.1

Connections of the fieldbus module 2112

INTERBUS loop

2112

IN

OUT

5

4

3

2

1

7

6

Fig. 4-1

Name/meaning of the module elements

No.

Name/Meaning

Yellow bus LED

Status: Bus communication

ON

Fieldbus module 2112 has been initialized
INTERBUS communication with the master is possible.

OFF

Fieldbus module 2112 is not supplied with voltage yet.

1

BLINKING
(4 Hz)

Peripheral fault/open circuit
Voltage supply from the INTERBUS-Loop, but no INTERBUS communication.

1

BLINKING
(2 Hz)

Voltage supply if INTERBUS communication is active. Error telegrams caused by, e.g. open circuit, are generated.

•

Module not connected to the controller or

•

initialization active.

BLINKING
(0.5 Hz)

Voltage supply (5 V) from INTERBUS-Loop, but no INTERBUS communication.

Green LED

ON

2112 fieldbus module is supplied with voltage and is connected to the controller.

OFF

The 2112 fieldbus module is supplied via INTERBUS-Loop.X

2

BLINKING

2112 fieldbus module is supplied with voltage but is not connected to the controller.
Controller is

•

switched-off,

•

being initialized or

•

not available

4

3

Green LED or red LED
Operating status of the controllers 82XX, 8200 vector and 93XX. (See Operating Instructions for the controller)

5

Fixing screw for fieldbus module

6

INTERBUS-Loop input (IN)

7

INTERBUS-Loop output (OUT)