1 controller is inhibited, Controller is inhibited, Troubleshooting and fault elimination – Lenze EMF2112IB User Manual

Page 42

Advertising
background image

Troubleshooting and fault elimination

7-2

BA2112EN

7.1

Controller is inhibited

The controller cannot be enabled via INTERBUS-Loop process data, i.e. the status ” OPERATION
ENABLED” will not be reached.

1

INTERBUS loop

Initialization

ok?

INTERBUS loop

check

Check 2112 mo-

dule

Yellow bus LED

on permanently?

82XX:

Set the operating mode (C0001) to

3 (if necessary, store parameter

C0003)

POW1 = 0000

hex

selection

PIW1 =

xxxx xxxx x100 0000

bin

(switch-on inhibit)?

PIW1 =

xxxx xxxx 0xxx 1000

bin

(fault)?

Fault (TRIP)

reset

No

Yes

No

Yes

No

Yes

Yes