5.4.2

DRIVECOM control

Tip !

•

As soon as the fieldbus module is attached to the 93XX controller, the controller is inhibited.
DRIVECOM sets the status SWITCH-ON INHIBIT.

•

Points 1. to 5. (see below):
– For enabling the controller, the status OPERATION ENABLE must be set once through the

DRIVECOM control word.

– The controllers 821X, 8200 vector and 822X need a speed setpoint to be enabled. These

controllers should therefore have a speed setpoint preselected via the corresponding
process data assignment before they are enabled through 7E

hex

or 7F

hex

.

1. Controller settings as described in chapter 5.3
2. DRIVECOM unit control preselection under parameter C0009

≠

11, 12

3. Change to status „ READY FOR SWITCH ON“

DRIVECOM control word = 0000 0000 0111 1110

bin

(7E

hex

).

4. Change to the status „ OPERATION ENABLED“

DRIVECOM control word = 0000 0000 0111 1111

bin

(7F

hex

)

(waiting for OPERATION ENABLED)

5. The controller is enabled.

5.4.2.1

Create DRIVECOM compatibility

(C0009

≠

11, 12)

The unit control is described in the DRIVECOM profile 20. In the following, you will find the changes required for the Lenze controllers.

820X

-

821X,
8200 vector
and 822X

The automatic DC-injection brake must be deactivated in all parameter sets, i. e.

•

C0106= 0

•

C2106= 0

•

C4106= 0 (only 8200 vector)

•

C6106= 0 (only 8200 vector)

If the automatic DC-injection brake is not deactivated (holding time of the DC-injection brake C0106 unequal 0), the controller automatically
switches from the status ”OPERATION ENABLED” to the status ”SWITCHED ON” when the speed is 0 and the holding time of the DC-injection
brake is elapsed. If the setpoint is higher than 0, the controller is automatically reset to the status ”OPERATION ENABLED”.

93XX

Set a DRIVECOM speed signal configuration under code C0005, e. g.:

•

C0005= 1013

This configuration corresponds to the signal configuration 1000 with the following changes:

•

Setpoint selection via INTERBUS-Loop

•

Unit control via INTERBUS-Loop

•

Output X5.A1 is selected as voltage output for the internal supply of the digital inputs.

•

Actual values and status signals for INTERBUS-Loop

For the detailed description of the signal configuration, see 93XX Manual.