Parameter setting, Show/hide bookmarks – Lenze EMF2112IB User Manual

Page 35

Advertising
background image

Parameter setting

6-13

BA2112EN

Controllers 82XX and 8200 vector (C0001 = 3) and 93XX

With INTERBUS-DP control (82XX: Lenze parameter C0001 = 3; 93XX: always) and when using the
2112 fieldbus module, the Lenze controller status is normalized according to the DRIVECOM-Profile
20.

Information about the current unit status (Fig. 6-4 rectangles in the status diagram) are available in
the DRIVECOM parameter “ Status word“ . Commands in the DRIVECOM parameter control word
can change the controller status. These commands are marked by arrows in the following diagram.

Inhibit voltage
xxxx xxxx xxxx xx0x

automatically, if the error reaction is over

Standstill
xxxx xxxx
xxxx x110

Standstill
xxxx xxxx xxxx
x110

Switch on
xxxx xxxx
xxxx x111

automatically when

initializing is completed

Reset fault
xxxx xxxx 0xxx xxxx

Switch on unit

Status word xxxx xxxx x0xx 0000

NOT READY TO SWITCH ON

READY TO SWITCH ON

Status word xxxx xxxx x01x 0001

SWITCHED ON

Status word xxxx xxxx x01x 0011

OPERATION ENABLED

Status word xxxx xxxx x01x 0111

Fault

Status word xxxx xxxx x0xx 1000

Example:
Status information by means of
„status word“
Bit 15 ... bit 0 (binary display)

SWITCH ON INHIBIT

Status word xxxx xxxx x0xx 0000

QUICK STOP ACTIVE

Status word xxxx xxxx x01x 0111

Operation enable
xxxx xxxx xxxx 1111 and
act. speed value

0*

Operation inhibit
xxxx xxxx xxxx 0111 or act.
speed value = 0*

Inhibit RFG is mapped to

quick stop

Quick stop

xxxx xxxx xxxx x01x

Quick stop
xxxx xxxx xxxx x01x

Inhibit voltage
xxxx xxxx xxxx xx0x

Standstill
xxxx xxxx xxxx x110

FAULT REACTION ACTIVE

Status word xxxx xxxx x0xx 1111

Malfunction was recognized

xxxx xxxx 1xxx xxxx

Inhibit voltage
xxxx xxxx xxxx xx01
or
quick stop completed

9

8

4

5

11

6

7

10

12

14

13

3

Note:
* only valid for 821X, 8200 vector when the automatic
DC-injection brake is active (C0106, C2106

0)

2

Fig. 6-4

Status diagram DRIVECOM unit control

Status

Meaning

NOT READY TO SWITCH ON

The controller is being initialized and is not yet ready to operate. It then automatically switches to the status READY TO SWITCH ON.

SWITCH ON INHIBIT

The controller is inhibited and waits for command 2 (shut down).

READY TO SWITCH ON

The controller is inhibited and waits for command 3 (switch on).

SWITCHED ON

The controller is inhibited and waits for command 4 (enable operation).

OPERATION ENABLED

The controller is enabled. In this status, a pulse inhibit can be set automatically.

FAULT REACTION ACTIVE

A fault (TRIP) was recognized and a fault response initiated.

FAULT

The controller is in the status “FAULT“ (TRIP).

QUICK STOP ACTIVE

While being in the status “OPERATION ENABLED“ the command “Quick stop“ was set. The controller is decelerated in a controlled
way (quick-stop ramp). After deceleration, the controller automatically changes to the controller status “SWITCH ON INHIBIT“.

The actual unit status can only be clarified by combining the unit-status information bits (bit 0 to 6).
This is shown in the following: