Troubleshooting and fault elimination

7-4

BA2112EN

7.2

Check INTERBUS-Loop

Short test of the INTERBUS-Loop system in the event of faulty initialization. The diagnostics
information of the INTERBUS-Loop fieldbus modules in the host must be considered.
For troubleshooting it can be reasonable to reduce the bus so that only one unit is connected to the
INTERBUS-Loop.

Switch on all units or

disconnect all units switched

off from the INTERBUS-Loop

Are all units

at the INTERBUS-Loop

switched on?

INTERBUS loop

initialization

ok?

Yes

Reduce the number of controllers

connected to INTERBUS-Loop
until the controller in question is

the last one connected.

Connect the next

controller

No

Yes

Replace the unit

No