2 unit control (c0009 = 11), 1 control word, Unit control (c0009 = 11) – Lenze EMF2112IB User Manual

Page 30: Control word, Parameter setting, 2 unit control

Advertising
background image

Parameter setting

6-8

BA2112EN

6.1.2

Unit control

(C0009 = 11)

In the following the bit assignment of control and status word is under C0009 = 11:

6.1.2.1

Control word

Control word for 82XX and 8200 vector

820X

821x,822x

8200vector

820X

821x,822x

Factory setting:

C0001= 3 if C0007 < 52

Factory setting:

C001= 3 if C0007 > 51

0

JOG1, JOG2, JOG3
00 = C0046 active
01 = JOG1 (C0037) active
10 = JOG2 (C0038) active
11 = JOG3 (C0039) active

JOG1, JOG2, JOG3
00 = C0046 active
01 = JOG1 (C0037) active
10 = JOG2 (C0038) active
11 = JOG3 (C0039) active

NSET1-JOG1/3
00 = C0046 active
01 = JOG1 (C0037) active
10 = JOG2 (C0038) active
11 = JOG3 (C0039) active

1

11 = JOG3 (C0039) active

11 = JOG3 (C0039) active

NSET1-JOG2/3

2

CW/CCW (CW rotation/CCW rotation)
0 = CW rotation
1 = CCW rotation

CW/CCW (CW rotation/CCW rotation)
0 = CW rotation
1 = CCW rotation

DCTRL1-CW/CCW
0 = not active
1 = active

3

QSP (quick stop)
0 = QSP not active
1 = QSP active

QSP (quick stop)
0 = QSP not active
1 = QSP active

AIF-CTRL-QSP
0 = not active
1 = active

4

Reserved

RFG stop (stop of the ramp function
generator)
0 = RFG stop not active
1 = RFG stop active

NSET1-RFG1-STOP
0 = not active
1 = active

5

Reserved

RFG zero (deceleration along the T i f
ramp C0013)
0 = RFG zero not active
1 = RFG zero active

NSET1-RFG1-0
0 = not active
1 = active

6

Reserved

UP function for motor potentiometer
0 = UP not active
1 = UP active

MPOT1-UP
0 = not active
1 = active

The default setting (see below) is
accepted with setting C0007 > 51
Use C0410 to set your own

7

Reserved

DOWN function for motor
potentiometer
0 = DOWN not active
1 = DOWN active

MPOT1-DOWN
0 = not active
1 = active

Use C0410 to set your own
configurations.

8

Reserved

Reserved

Reserved

9

Ctrl. inhibit (controller inhibit)
0 = controller not inhibited
1 = controller inhibited

Ctrl. inhibit (controller inhibit)
0 = controller not inhibited
1 = controller inhibited

AIF-CTRL-CINH
0 = not active
1 = active

10

Reserved

Reserved

No function

11

Reserved

TRIP reset
0 -> 1 = Edge from 0 to 1

AIF-CTRL-TRIP-RESET

0 -> 1 = Edge from 0 to 1

12

PAR1 (Parameter set changeover)
0 -> 1 = Parameter set
1 -> 0 = Parameter set

PAR1 (Parameter set changeover)
0 -> 1 = Parameter set
1 -> 0 = Parameter set

DCTRL1-PAR2/4
0 = not active
1 = active

13

Reserved

Reserved

DCTRL1-PAR3/4
0 = not active
1 = active

14

DC brake (DC injection brake)
0 = DC brake not active
1 = DC brake active

DC brake (DC injection brake)
0 = DC brake not active
1 = DC brake active

MCTRL1-DCB
0 = not active
1 = active

15

Reserved

Reserved

Reserved