Parameter setting

6-2

BA2112EN

Assignment of process input data words

Meaning for

Byte No.

Unit control

C0009 = 11

DRIVECOM control

C0009

11, 12

User defined

control profile

C0009 = 12

(only 8200 vector / 93XX)

1 HIGH byte; bit 8-15

PIW1

DRIVECOM stat s word

DRIVECOM stat s word

Link: W1 to AIF-OUT

2 LOW byte; bit 0-7

PIW1

DRIVECOM status word

DRIVECOM status word

Link: W1 to AIF-OUT

1 HIGH byte; bit 8-15

PIW2

82XX / 8200 vector:

Actual speed

Link: W2 to AIF-OUT

2 LOW byte; bit 0-7

PIW2

82XX / 8200 vector:

Actual speed

93XX:

Freely configurable

Link: W2 to AIF-OUT

6.1.1.2

Process-data assignments for 82XX

Structure of the PO-data response (data to drive)

Byte 1

Byte 2

Byte 3

Byte 4

Control word
High byte

Control word
Low byte

Setpoint
High byte

Setpoint
Low byte

Control word: see chapter 6.1.3.2

Setpoint: frequency setpoint
Here the frequency setpoint is preselected as process data word. The normalization is here
indicated as signed value with

б

24000 =

б

480 Hz.

Structure of the PI data response (data from drive)

Byte 1

Byte 2

Byte 3

Byte 4

Status word
High byte

Status word
Low byte

Actual value
High byte

Actual value
Low byte

Status word: see chapter 6.1.3.3.

Actual value: act. frequency value
The actual frequency value is provided as signed normalization

б

24000 =

б

480 Hz.