3 process-data assignment for 8200 vector, Process-data assignment for 8200 vector, Parameter setting – Lenze EMF2112IB User Manual

Page 25

Advertising
background image

Parameter setting

6-3

BA2112EN

6.1.1.3

Process-data assignment for 8200 vector

Digital and analog input and output signal can be configured freely (see Operating Instructions “ 8200
vector” : Codes C0410, C0412, C0417 and C0421).

The change of the code C0001 to 3 starts the preconfiguration of the process data words in the
controller (see chapter 5.3,

(

›

5-2)

).

Structure of the PO-data response (data to drive)

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Control word
High byte

Control word
Low byte

AIF-IN.W1
High byte

AIF-IN.W1
Low byte

AIF-IN.W2
High byte

AIF-IN.W2
Low byte

Control word: see chapter 6.1.3.2.

AIF-IN.Wx see C0412.

Structure of the PI data response (data from drive)

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Status word
High byte

Status word
Low byte

AIF-OUT.W1
High byte

AIF-OUT.W1
Low byte

AIF-OUT.W2
High byte

AIF-OUT.W2
Low byte

Status word: see chapter 6.1.3.3.

AIF-OUT.Wx see C0421.

Tip!

Frequency and speed are normalized with

б

24000

 б

480 Hz.

Torque is normalized with 16384



100% .

Show/Hide Bookmarks

Advertising