4 user defined control profile (c0009 = 12), 2 process data monitoring, 1 process data monitoring time – Lenze EMF2112IB User Manual

Page 40: 2 process data monitoring selection code, User defined control profile (c0009 = 12), Process data monitoring, Process data monitoring time, Process data monitoring selection code, Parameter setting

Advertising
background image

Parameter setting

6-18

BA2112EN

6.1.4

User defined control profile

(C0009 = 12)

Only useful with 93XX and 8200 vector (free configuration possible)

When using a user-defined control profile, predefined control and status words are not
available.

The user determines the link between input and output data.

Function block assignment for 93XX (see chapter 6.1.1.4,

(

›

6-4)

)

– Byte 3 and 4 form the input or output word W1
– Byte 5 and 6 form the input or output word W2

Process data assignment for 8200 vector: see chapter 6.1.1.3,

(

›

6-3)

.

For more information about the function blocks see the Manuals 93XX and 8200 vector.

Danger!

User-defined control is only allowed for 93XX and 8200 vector controllers!

If a speed has been selected via the corresponding process data word, the drive starts immediately
when the module is being attached.

Tip!

Please observe that bytes 7/8 of the control/status word shown in the diagram above cannot be
accessed via INTERBUS-Loop.

6.2

Process data monitoring

6.2.1

Process data monitoring time

If the process data transfer takes longer than t = 640 ms, the action set under parameter C0125
(Process data monitoring selection code) will be activated.

6.2.2

Process data monitoring selection code

Code

Meaning

C0125

0: No action
1: No action
2: Unit control command “Inhibit voltage” (controller inhibit with latching in status “SWITCH ON INHIBIT”).
3: Unit control command “Quick stop” (QSP) with latching in status “SWITCH ON INHIBIT”

Danger!

DRIVECOM control
– The latching function is active.

Unit control
– The latching function must be implemented in the master!

Otherwise the machine starts automatically after the bus system has been activated if a
speed setpoint

0 has been set in the process data word.