DRIVECOM control

(C0009

11, 12)

6.1.3.1

DRIVECOM status machine

Controllers 82XX, 8200 vector (C0001

½

3)

For standard control you enter the control information via the corresponding control inputs
(terminal):

Information about the current unit status (Fig. 6-3, see below) (rectangles) are available in the
DRIVECOM parameter “ status word“ . Commands in the DRIVECOM parameter “ control word“ are
switched off and cannot change the controller status. The commands to change the controller status
are entered via the corresponding control inputs. These commands are marked by arrows in the
following diagram.

Status word xxxx xxxx x0xx 0000

NOT READY TO SWITCH ON

QSP**

Ctrl. enable**

Ctrl. inhibit**

automatically when
the initialization is
completed

TRIP (fault)

TRIP reset**

Switch on unit

READY TO SWITCH ON

Status word xxxx xxxx x01x 0001

SWITCHED ON

Status word xxxx xxxx x01x 0011

OPERATION ENABLED

Status word xxxx xxxx x01x 0111

automatically

Fault

Status word xxxx xxxx x0xx 1000

Note:
The terms marked with ** are
commands

Fig. 6-3

Status diagram for standard unit control

Status

Meaning

NOT READY TO SWITCH
ON

The controller is being initialized and is not yet ready to operate.
It then automatically switches to the status READY TO SWITCH ON.

READY TO SWITCH ON

The controller is inhibited and waits for the power stage to be charged. It then automatically switches to the status “SWITCHED ON“.

SWITCHED ON

The controller is inhibited and waits for controller enable.

OPERATION ENABLED

The controller is enabled. In this status, a pulse inhibit can be set automatically.

FAULT

The controller is in the status “FAULT“ (TRIP).