Parameter setting – Lenze EMF2112IB User Manual

Page 36

Advertising
background image

Parameter setting

6-14

BA2112EN

Unit status

Bits of the status word

Bit

6

5

4

3

2

1

0

NOT READY TO SWITCH ON

0

0

0

0

0

SWITCH ON INHIBIT

1

0

0

0

0

READY TO SWITCH ON

0

1

0

0

0

1

SWITCHED ON

0

1

0

0

1

1

OPERATION ENABLED

0

1

0

1

1

1

FAULT

0

1

0

0

0

FAULT REACTION ACTIVE

0

1

1

1

1

QUICK STOP ACTIVE

0

0

0

1

1

1

Switch-on inhibit

Quick stop

Voltage inhibit

Fault

Operation enabled

Switched on

Ready to switch on

Command

Meaning

COMMAND 2, 6, 8 (standstill)

Control word: bit 0 = 0

Command to change from different states to the status „READY TO SWITCH ON“.

COMMAND 3 (switch on)

Command to change to the controller status “SWITCHED ON“.

COMMAND 4 (enable operation)

Command to change to the controller status “OPERATION ENABLED“. The controller inhibit is deactivated.

COMMAND 5 (inhibit operation)

Command to change to the controller status “SWITCHED ON“. The controller inhibit is activated.

COMMAND 7, 9, 10, 12 (voltage inhibit)

Control word: bit 1 = 0

Command to change to the controller status “SWITCH ON INHIBIT“. The controller inhibit is activated.

COMMAND 7, 10, 11 (quick stop)

Control word: bit 2 = 0

Command to change to the controller status “SWITCH ON INHIBIT“. If the controller was enabled, it is decelerated in a
controlled way along the Lenze quick-stop ramp.

COMMAND 13 (FAULT/TRIP)

The controller has recognized a malfunction. For some malfunction a controlled deceleration may be necessary
(depending on the controller). Once completed, the controller changes to the status FAULT.

COMMAND 14 (reset fault/TRIP)

Control word: bit 7 = 0

A 1

With the series 821X, 8200 vector this command acknowledges a fault. The controller changes to the status “SWITCH ON
INHIBIT“ when a fault is no longer recognized.