Function library lenzeiosystem.lib, Application examples – Lenze DDS Function library IOSystem User Manual

Page 12

Advertising
background image

3.1

Modular decentralised I/O system

Function library LenzeIOSystem.lib

Application examples

3−2

L

LenzeIOSystem.lib EN 1.7

Then the Parameter program that must be generated in the SFC editor follows. With the invocation
of the function block instance, the step Parameter_data has the action generated in the FBD editor.

Note!

·

Enter a minimum time of ten seconds for step Init via the menu command Extras

ÞStep

attibutes.... Correct entry: T#10s

Make sure that step Parameter_data is not executed before the initialisation phase of the I/O system
is complete. This is achieved with a minimum time of ten seconds.

As this POU must be processed cyclically, the program is invoked in the PLC_PRG (main program).
The sequential function chart ensures a cyclic task.

The parameterisation process is started via the initial action in step Parameter_data.

Once the parameterisation is complete, the final action in step Parameter_data sets input bExecute
to FALSE and variable bStart to TRUE.

Variable bStart ensures that step Parameter_data is executed

·

on switching on

·

on reset and subsequent starting.

When the parameterisation is complete, the PLC_PRG (main program) stops in step Init. It does not
impose an extra burden on the target system during subsequent program operation.