Function library LenzeIOSystem.lib

Function blocks

4.10

L_IOParCompactModule − Parameterisation function

4−27

L

LenzeIOSystem.lib EN 1.7

(Variable type: VAR_INPUT)

ð Inputs
Variable name

Information/possible settings

Data type

wCobID_RxPDO1

Word

Set identifiers
Default values: Input setting = 0
RxPDO = I/O system receive identifiers
Identifiers can be given any setting with a specified value.
The identifiers are composed as follows if the input setting = 0.
Note!
The basic identifiers are outside the preassigned standard system bus range.
ID range: 384−831
This prevents IDs from coinciding with unassigned CAN objects on which the IO−lib is
based.

RxPDOX

Identifier =

Basic ID +

Node address

RxPDO1

837

835

2

byTransmissionType_RxPDO1

Byte

Transmission method

0 Event−controlled

1 Time−controlled

2 Event−controlled with superimposed cycle time

tCyceTime_TxPDO6

...

tCyceTime_TxPDO10

Time

Cycle time t = 0 − 65535 ms

wCobID_TxPDO1

Word

Set identifiers
Default values: Input setting = 0
TxPDO = I/O system receive identifiers
Identifiers can be given any setting with a specified value.
The identifiers are composed as follows if the input setting = 0.
The basic identifiers are outside the preassigned standard system bus range.
ID range: 384−831
This prevents IDs from coinciding with unassigned CAN objects on which the IO−lib is
based.

TxPDOX

Identifier =

Basic ID +

Node address

TxPDO1

838

836

2

byTransmissionType_TxPDO1

Byte

Transmission method

0 Event−controlled

1 Time−controlled

2 Event−controlled with superimposed cycle time

tInhibitTime_TxPDO6
...
tInhibitTime_TxPDO10

Time

Inhibit time t = 0 − 65535 ms

tCyceTime_TxPDO6

...

tCyceTime_TxPDO10

Time

Cycle time t = 0 − 65535 ms