Function library LenzeIOSystem.lib

Function blocks

4.2

L_IOParAlnModule − Parameterisation function

4−5

L

LenzeIOSystem.lib EN 1.7

ð Inputs

(Variable type: VAR_INPUT)

Variable name

Data type

Information/possible settings

bExecute

BOOL

Execute write request

FALSE

ä TRUE Write request is executed

byNodeAdr

Byte

Device address: 1 − 63

byAnalogModuleNo

Byte

Slot number

·

The analog module that is mounted first has the slot number 1.

·

Maximally 16 analog modules can be attached.

bEnableDiagnosticAlarm

BOOL

Enable diagnostics alarm

TRUE Diagnostics alarm is enabled

bEnableAnalogInterrupt

BOOL

Enable analog data transmission

TRUE Data transmission is enabled

byFunctionInput_CH1

...

byFunctionInput_CH4

Byte

Parameterise function

Default ±10V function code = 3B

h

^ 6−1

bySampleRate_CH1

...

bySampleRate_CH4

Byte

Select number of conversions per second

0 15 conversions

1 30 conversions

2 60 conversions

3 123 conversions

4 168 conversions

5 202 conversions

6 3.7 conversions

7 7.5 conversions

bySelectionFcn_CH1

...

bySelectionFcn_CH4

Byte

Selection

0 Selection deactivated

1 Use 2 of 3 values

2 Use 4 of 6 values

byHysterese_CH1

...

byHysterese_CH4

Byte

Hysteresis

0 Hysteresis deactivated

1 Hysteresis ±8

2 Hysteresis ±16

byTriggerSelection_CH1

...

byTriggerSelection_CH4

Byte

Transmission result

0 Use default settings

1 Upper limit value exceeded

2 Lower limit value not reached

3 Input value has changed by a defined value.

byTriggerValue_CH1

...

byTriggerValue_CH4

DWORD

Value selection for a transmission event

2 Default