L_IOParSSIModule − Parameterisation function

Function library LenzeIOSystem.lib

Function blocks

4−12

L

LenzeIOSystem.lib EN 1.7

4.5

L_IOParSSIModule − Parameterisation function

The SSI interface (SSI = Synchronous Serial Interface) is a synchronously clocked interface.

Function block L_IOParSSIModule converts the serial information of the measured values into
parallel information that is subsequently supplied to the control system.

byFunction_Baudrate

bFunction_Code

L_IOParSSIModule

bExecute

byNodeAdr

nState

CTRL

byAnalogModuleNo

bFunction_Hold

EPM-T110

Ixxxh

bFunction_SetDigitalOut

ð Inputs

(Variable type: VAR_INPUT)

Variable name

Data type

Information/possible settings

bExecute

Bool

Execute write request

FALSE

ä TRUE Write request is executed

byNodeAdr

Byte

Device address: 1 − 63

byAnalogModuleNo

Byte

Slot number

·

The first analog module installed is assigned slot number 1.

·

A maximum of 9 modules may be plugged.

byFunction_Baudrate

Byte

Baud rate setting

0 300 kbps

1 100 kbps

2 300 kbps

3 600 kbps

4 300 kbps

bFunction_Code

Bool

Coding

Default 0 Binary code

1 Gray code

bFunction_Hold

Bool

Hold function

0 Not active

1 Active

bFunction_SetDigitalOut

Bool

Digital outputs

0 Not active

1 Active