6.3

Signal functions for analog inputs and outputs EPM−T330

Function library LenzeIOSystem.lib

Appendix

6−8

L

LenzeIOSystem.lib EN 1.7

Parameter
bytes 2/3/4/5

Tolerance

1)

Format

Signal range

Signal function

04

h

Current signal output

4 ... 20 mA

+4.00
0

{0.01 mA}

{1 dec}

+20.00

+16384

B

±0.8 % of limit value

Lower range limit:

+0.00 mA

−4096

dec

Upper range limit:

+24.00 mA

+20480

dec

06

h

Current signal output

0 ... 20 mA

0.00
0

{0.01 mA}

{1 dec}

+20.00

+16384

B

±0.6 % of limit value

Lower range limit:

Upper range limit:

+25.00 mA

+20480

dec

0B

h

Current signal output
(complement on two)

±20 mA

−20.00
−27648

{0.01 mA}

{1 dec}

+20.00

+27648

A

±0.3 % of limit value

Lower range limit:

−23.52 mA

−32512

dec

Upper range limit:

+23.52 mA

+32511

dec

0C

h

Current signal output
(complement on two)

4 ... 20 mA

+4.00
0

{0.01 mA}

{1 dec}

+20.00

+27648

A

±0.8 % of limit value

Lower range limit:

+0.00 mA

−6912

dec

Upper range limit:

+22.81 mA

+32511

dec

0E

h

Current signal output

0 ... 20 mA

0.00
0

{0.01 mA}

{1 dec}

+20.00

+27648

A

±0.6 % of limit value

Lower range limit:

Upper range limit:

+23.52 mA

+32511

dec

FF

h