Function library LenzeIOSystem.lib

Function blocks

4.5

L_IOParSSIModule − Parameterisation function

4−13

L

LenzeIOSystem.lib EN 1.7

Outputs

ð

(Variable type: VAR_OUTPUT)

Identifier

Data type

Value/meaning

nState

Integer

States
If a transmission error occurs during the parameterisation process, or the input data
are incorrect, the parameterisation process is aborted and an error number is
indicated at output nState.
Any errors are reset via an edge reversal at input bExecute or on
program restart.

0 Transmit command is executed.

The module is parameterised.

1 Transmit command sent

Processing in process

2001 Error occurred during bus transfer

2002 Transmit command timed out

2004 Access denied

Wrong target system: Subindex does not exist

2005 Access denied

Wrong target system: Index does not exist

2013 Access denied

Wrong target system: Invalid value range

2111 Access denied

Wrong target system: More than 4 digits specified after
comma, or no fixed−comma−format index

2117 Communication channel does not exist

Set byCom channel

−10xx Incorrect value at function block input.

XX := Number of faulty input (counting direction down),
parameterisation impossible.
Remedy: Change input value, restart data transmission